Model# 467
600V
Low Voltage Potential Transformer
- Terminals are 6-32 screws with cupwashers.
- The core and coil assembly is encased in a thermoplastic case and filled with resin.
- These transformers are designed for operation line-to-line. They may also be operated line-to-ground, or line-to neutral, at reduced voltage (58% of rated volts).
- It is desirable to use the proper size fuse in the secondary to protect the P.T. Use a 0.40 Amp fuse with Model 467
- With two exceptions these transformers are ANSI C57.13 group 1. Those marked * are group 2.
Overview
Insulation Class 0.6kV ā 10kV BIL
Thermal Rating40VA at 30Ā°C Amb. ā 27VA at 55Ā°C Amb. (60Hz)
Weight4.0 Lbs
Accuracy
Accuracy ClassĀ±1% at all burdens up to 5VA at 1.0 and 0.95 P.F.
Input
Volts0-69.3V thru 0- 600V
Frequency60Hz
Output
Standard120V
245941
E238872
Need Assistance? Call: 614-889-6152