Model# 467 600V

Low Voltage Potential Transformer

  • Terminals are 6-32 screws with cupwashers.
  • The core and coil assembly is encased in a thermoplastic case and filled with resin.
  • These transformers are designed for operation line-to-line. They may also be operated line-to-ground, or line-to neutral, at reduced voltage (58% of rated volts).
  • It is desirable to use the proper size fuse in the secondary to protect the P.T. Use a 0.40 Amp fuse with Model 467
  • With two exceptions these transformers are ANSI C57.13 group 1. Those marked * are group 2.

Overview

Insulation Class 0.6kV ā€“ 10kV BIL
Thermal Rating40VA at 30Ā°C Amb. ā€“ 27VA at 55Ā°C Amb. (60Hz)
Weight4.0 Lbs

Accuracy

Accuracy ClassĀ±1% at all burdens up to 5VA at 1.0 and 0.95 P.F.

Input

Volts0-69.3V thru 0- 600V
Frequency60Hz

Output

Standard120V

467-low-voltage-potential-transformer

  • RoHS

  • CSA

    245941

  • C RU US

    E238872

Need Assistance? Call: 614-889-6152

Detailed Model Specifications

Click below to see available detailed specifications

While these tables work on mobile devices, they are best viewed on a desktop computer.