ACTR Series Current Transducer
Model# ACTR

RMS Current Transducer

Request Quote
Detailed Model Specs
SPECIFICATIONS

INPUT
Frequency Range:  48 to 420Hz
Burden:  0.28VA F.S.
Current Overload
– 1-10A Range:  2 X F.S. (cont.)
– 15-20A Range:  25A Maximum,continuous
– 10 X Rating:  (1 sec. transient) 10 Seconds/hour
Dielectric Test:  (Input/Output/Case)  2200Vac

OUTPUT
Output Ripple:  
<1.0% F.S.
Response:  (90%) 100ms
Output Loading (Ω)
– 0-1mA:  0-10K
– 0-10Vdc, 0-5Vdc:  2K min.
– 4-20mA:   0-500
Field Adjustable Cal:   ± 10%

ACCURACY – (Includes effects of linearity and setpoint.)
– ± 0.25% F.S. @ 60Hz
– ± 0.5% over frequency range (typ.)
Temperature Effect: (-20° C to +60° C) ± 1.0% Rdg.
Instrument Power:  (Std.)115Vac, ± 15%, 50-60Hz, 3.5VA
Weight:  1.5Lbs.

APPLICATIONS
  • For use in applications where measurement of non-sinusoidal waveforms is required.
  • Designed to withstand motor start-up transients.
FEATURES
  • Accurate measurement of the true RMS value of input signals over a wide frequency range.
  • Input/output isolation.
  • C UL US Listed

    E500652