Model# CRD-005 Current Relay

DC Current Relay w/ Setpoint

OPERATIONS MODE:

  • Under Range Alarm: The output relay will energize when instrument power is applied and the current is above the set point threshold. It will remain in a ā€œFail Safeā€ mode until either the input current drops below the set point threshold or instrument power is removed.
  • Over Range Alarm : The output relay will energize when instrument power is applied and will remain in a ā€œFail Safeā€ mode until either the instrument power is removed or the input current exceeds the set point threshold level.

FEATURES:

  • Programmable settings for either current or voltage input, threshold levels and over or under relay alarms.
  • Internal DIP switches may be set for either 0 ā€“ 1mAdc or 0 ā€“ 10Vdc, and may be set for under alarm or over alarm relay operation.
  • Lid mounted two digit numerical push-button switch calibrated as percent of full-scale with a threshold range of 01 ā€“ 99 percent.
  • Red LED lamp lights to indicate when threshold level has been obtained.
  • Highlighted area indicates Factory Setting. Unit is set at factory for the 0-1mA input and in the over range alarm mode.

Overview

Response Time10Āµs
Set Point (Digital)01 ā€“ 99 %, 01 minimum
Dielectric Test (Input/Output/Case)1500Vac
Instrument Power85-135Vac, 50-400Hz, 2.5VA
Temperature Effect(-10Ā°C to +60Ā°C): Ā± 0.1%/OC

Accuracy

ClassSet point Ā± 2 digits

Input

Current Range1mAdc
Burden @ 1mAdc1K(Ī©)
Voltage0-10Vdc
Burden @ 0-10Vdc10K(Ī©)

Output

RelayForm C, SPDT
Rating120Vac, 3 Amps
Mechanical Operations1 Million

Model# CRD-005-Current-Relay

Need Assistance? Call: 614-889-6152

While these tables work on mobile devices, they are best viewed on a desktop computer.