GFP Ground Fault Current Monitor
Model# GFP | 600V Class

Ground Fault Current Monitor

Request Quote

SPECIFICATIONS

Operation Range: Trip Currents 5-60, 30-360, and 100-1200A
Time Delay: Instantaneous to 1 second
Input Power: 2VA plus shunt coil requirements
Input Withstand: 200kA RMS for 3 cycles, 50/60Hz
Nominal Input Voltage: 120Vac, 125Vdc, 48Vdc, or 24Vdc
Ambient Temperature Range: -30°C to +60°C
Weight: 3 Lbs

APPLICATIONS

These class 1 ground fault relays and sensors are used together to provide a system for detecting ground fault current in a grounded AC power system. When the system detects a ground fault that reaches a pre-selected current level and time delay, the relay initiates a trip signal to a shunt trip disconnect device that will open and clear the fault.

FEATURES
  • Optional zone interlocking
  • Integral test panel with “Push to Test” and “Shunt
    Trip Bypass”
  • Power on indication (LED)
  • Real time fault current level indicator
  • Positive visual trip indicator
  • Adjustable time delay
  • Discrete current threshold adjustment
  • Panel or door mounted
  • Clear plastic cover
  • Electro-mechanical relay output
  • Optional “Form C” relay contacts
  • Meets NEC Service
  • CSA

    245941

  • C UL US Listed

    E234818