Model# CTC AC Current Transducer/Transformer
Model# CTC

AC Current Transducer/Transformer

Request Quote
Detailed Model Specs
SPECIFICATIONS

INPUT
Current Range: 0-5A to 0-50A
Current Overload:
– 1.3X Rating Continuous
– 5X Rating for 10 sec./Hr.
Frequency: 50-60Hz
Dielectric Test: (Input/Output/Case) 1800Vac
Instrument Power:
– 0-5V; 0-10V Models: Self-Powered
– 4-20mA Models: Loop Powered, 24Vdc, ±4Vdc

OUTPUT:
– 5Vdc
– 10Vdc
– 4-20mA
Load on Output
– 0-5V, 0-10V Models >10MΩ
– 4-20mA Models) 0 to 500Ω
Ripple: <±0.5% F.S.
Response Time 90%:
– Typical) 300ms
– 5A; 10A <750ms

ACCURACY: 0.25%F.S.
– Includes Linearity, Set Point and Repeatability@60Hz
– Temperature Effect: (-20°C to +60°C) ±1%Rdg

FEATURES

The CTC Series of AC Current Transducers provide a self-powered 0-5Vdc or 0-10Vdc output or a loop-powered 4-20mAdc output proportional to window amperes. The output is derived from the average absolute value of the input and calibrated to the RMS value of a sine wave input.

  • Insensitive to polarity
  • Designed for applications requiring accurate current measurements
  • Easy to install
  • CE

  • C UL US Listed

    E500652