SPECIFICATIONS
  • Frequency: 50-400Hz
  • Insulation Level: 5.6kV, 60kV BIL Full Wave
  • Continuous Thermal Current Rating Factor:1.50 at 30°C Amb., 1.33 at 55°C amb.
    Except:
    250:5–1.00 at 30°C Amb., 0.85 at 55°C Amb.
    150:5 and 600:5–1.33 at 30°C Amb., 1.00 at 55°C Amb.
  • Primary Terminals: 1/2-13 Bolts with one Belleville washer
  • Secondary Terminals: Brass Studs No. 10-32 one flat washer,lock washer and regular nut
  • Weight: 20 lbs.
APPLICATIONS

Recommended Minimum Spacing:

  • A = Unit to Unit = 0.75″ minimum
  • B= HV to Ground in Air = 3.00″ minimum.

Recommended spacing are for guidance only. User needs to set appropriate values to assure performance for high potential test, impulse test, high humidity, partial discharge, high altitude, and other considerations like configuration.

FEATURES
  • UL Recognized
  • Metering and Relay Class (T50)
  • Short circuiting secondary terminal cover
  • Vacuum cast in polyurethane resin
  • FOR INDOOR USE ONLY.
  • Manufactured to meet the requirements os ANSI/IEEE C57.13
  • CSA

    LR89403

  • C RU US

    E145172