Model# 475 600V

Low Voltage Potential Transformer

  • The primary and secondary terminals are #8 brass screws, one lock washer and one flat washer.
  • The core and coil assembly is encased in a thermoplastic shell and filled with resin.
  • These transformers are designed for operation line-to-line. They may also be operated line-to-ground or line-to-neutral, at reducedĀ Ā Ā  voltage, (58% of rated volts).
  • It is desirable to use a 3.0 amp BBS type fuse in the secondary to protect the transformer.
  • When only one fuse is used, it must be connected into the line side (H1) terminal wiring. This will prevent the presence of voltage at the H1 terminal for a ruptured fuse in the neutral (H2) terminal wiring for line-to-neutral connected transformers.

Overview

Insulation Class0.6kV ā€“ 10kV BIL
Thermal Rating300 VA at 30Ā°C Amb. ā€“ 200 VA at 55Ā°C Amb. (60Hz)
Weight12.5 Lbs

Accuracy

Accuracy Class0.3W. ā€“ 0.6X. ā€“ 1.2M

Input

Volts0-69.3V thru 0- 600V
Frequency60Hz

Output

Standard120V

475-low-voltage-potential-transformer

  • CSA

    LR89403

  • RU

    E93779

Need Assistance? Call: 614-889-6152