ACT_005A Current Transducer from Flex-Core
Model# ACT

AC Current Transducer

Request Quote
Detailed Model Specs

SPECIFICATIONS

INPUT
Frequency Range:
 50/60Hz
Burden:  1.0VA F.S.
Current Overload:  2 X F.S. Rating continuous
20A model:  1.25 X F.S. Rating continuous
Dielectric Test:  (Input/Output/Case) 2200Vac
Instrument Power:
– STD. 4-20mA UNITS:  115Vac, 50/60Hz, ± 15%, 10VA max.
– “-22” Option:  230Vac, 50/60Hz, ± 15%, 10VA max.
Weight:
– A, C, CX5, and E2 Models  0.8Lb.
– E Models:  1.4Lbs.

OUTPUT ACCURACY – (Includes effects of linearity and set point.) ± 0.25% F.S. @ 60Hz
Output Ripple:  < 1.0% F.S.
Response:  400ms
Output Loading (Ω):
– 1mA:   0-10K
– 4-20mA (E Models):  0-1K
– 4-20mA (E2 Models):   0-600O @ 24Vdc
– 5V & 10V:  > 10M
Field Adjustable Cal:  ± 5%
Temperature Range:  -20° C to +60° C
Temperature Effect:  ± 1.0% Rdg.

APPLICATIONS
  • Designed for use in applications which require inexpensive current measurement.
  • Designed to withstand motor start-up transients.
FEATURES
  • Accurate, reliable current measurement over a frequency range of 50/60Hz
  • UL, CUL, and CE listed
  • CE

  • C UL US Listed

    E500652