MCT5 Current Transducer from Flex-Core
Model# MCT5

AC Current Transducer

Request Quote
Detailed Model Specs

SPECIFICATIONS

INPUT
Frequency Range: 48 to 65Hz, 60Hz Nom.
Burden:
– 1 Amp models @ 0.05VA
– 5 Amp models @ 0.175VA
Current Overload
– 2 X Full Scale Rating: (continuous)
-10 X Full Scale Rating: (10Sec./Hr.)
Dielectric Test (Input/Output): 1500Vac

OUTPUT
Output Ripple: <1.0% F.S.
Response Time: @ (99%) 400ms
Field Adjustable Span: ±5%
Termination: Wire Size 22 to 12 AWG

OUTPUT LOADING (Ω)
– 4-20mA: 0-500
– 4-20mA: (24V Loop Power) 0-600
Field Selectable:
– 0-1mA: 0-10K
– 0-5Vdc: >5M
– 0-10Vdc: >10M

ACCURACY (@ 60Hz): ±0.25% F.S.
– Includes effects of linearity and set point.
Temperature Effect: (-20°C to +65°C) ±1.0%
E Output: (-20°C to +40°C) ±1.0%
Instrument Power 4-20mA: 85-135Vac, 50/60Hz,3.0VA
Loop Powered: 15-40Vdc
Weight: 0.4Lbs.

APPLICATIONS
  • Ideal for use in enclosures with dimensional constraints.
  • Designed for industrial environments.
  • OEM measurement systems.
  • Designed for use with current transformers.
  • Easily integrated into control systems.
FEATURES
  • Ruggedized Polyamide DIN mount case.
  • Slim profile allows maximum use of available space.
  • Field selectable analog outputs. “A” Models only.
  • Recessed terminals provide increased safety.
  • RoHS

  • C UL US Listed

    E500652