Model# MVTR

RMS Voltage Transducer

Transducer output is derived from the RMS value of the input. DIN-rail lengths available: Consult Factory

Request Quote
Detailed Model Specs

Available Downloads

Download Datasheet
Download Product Catalog
View Whitepapers & Application Notes

Need Assistance? Give us a call: 614-889-6152

SPECIFICATIONS

INPUT
Voltage: 0-150 to 0-600 ac
Frequency Range: 50-400Hz
Burden:
– 150Vac Models: 1.0VA
– 300Vac, 600Vac Models-: 2.0VA
Voltage Overload: Full Scale Rating

OUTPUT
Scaling: 0-F.S. Input = 4-20mAdc Output
Response (to 90%):
150V & 300 models: 200ms
– 600V models: 500ms
Loading: (@24Vdc. Instr. Pwr) 0-500O
Set point Adjustment: ±5%, minimum
Output Ripple:  <1.0% pk-pk
Temprature Range:  -20°C to +60°C
Effect: ±1.0% F.S.

DIELECTRIC TEST
Input/Output: 2200Vac

INSTRUMENT POWER – (looped power)
– Nominal :24Vdc
– Range: 15-35Vdc

Output Ripple:  <1.0% pk-pk
Temperature Range:  -20°C to +60°C
Temperature Effect: ±1.0% F.S.
Termination Wire Size: 22 to 12 AWG
Weight:
150Vac, 300Vac- 0.25 Lb.
– 600Vac models with PT: 0.90 Lb.

ACCURACY (Includes effects of linearity and setpoint)
– 60Hz: 10-100% F.S:  ±0.25% F.S.
– All others:  ±1.0% F.S.

APPLICATIONS
  • True RMS transducer for accurately sensing voltage in single and 3-phase installations
  • Ideal for non sinusoidal applications
  • Designed for industrial environments
FEATURES
  • Provides a fully-isolated 4-20mAdc output proportional to the measured voltage, even in non-sinusoidal waveforms
  • Slim profile allows maximum use of control enclosure space
  • Recessed terminals provide increased safety
  • UL94V-0 polyamide DIN-mount case style