SPECIFICATIONS

INPUT
Voltage: 0-0.050 to 0-4000V
Over Range: 20% of Rating
Burden: 1mA

INSTRUMENT POWER
– Standard:
115V, 50/60Hz, 3VA
Dielectric Test:
– (input/output/case):  10kVac
– (instr. power to output):  2200Vac

INPUT LEADS
Wire size:  22 AWG
Length:  Standard: 3′
Option “L”:  15′

OUTPUT (UNIDIRECTIONAL)
Response (90%): 100ms
Loading:
– 1mAdc =10K Ω
– 5Vdc, 10Vdc =2K Ω
– (-20mAdc) =500 Ω
Temp. Effect: (-10°C to +60°C) ±1.0% Rdg., ±0.1% F.S.
Weight:  3.0Lbs.

ACCURACY
– Standard: +0.5% F.S.

APPLICATIONS
  • Monitoring of substation or electric circuit performance.
  • Isolation and amplification of shunt output.
FEATURES
  • Output is electrically isolated from the input and is directly proportional to the input amplitude.