Model# PC5 Single Phase AC Watt Transducer
Model# PC5

Single Phase AC Watt Transducer

Request Quote
Detailed Model Specs
Download Datasheet
SPECIFICATIONS

INPUT
Frequency Range:
PC5: 48 to 70Hz

Power Factor: Any
Response (Transient 90%)
Internal sensors: < 100µs
Current transformers: 1ms

Burden
Voltage and Current: 1.25VA/Phase
Output amplifier: 2 Watts
Current Overload
Continuous: 1-10A: 2 X F.S.
15A, 20A, and 25A: F.S.
Transient: 6 X F.S. (10 sec.)
Dielectric Test: (Input/Output/Case) 1500Vac (RMS)
Surge: Withstands IEEE SWC test
OUTPUT
ACCURACY:± 0.5% F.S.
Includes combined effects of power factor, linearity,repeatability and current sensor.

Output Ripple: <1% F.S.
Output Loading (O)
0-1mA: 0-10K
0-10Vdc: 2K min.
4-20mA (E): 0-1500
4-20mA (E2): (@24Vdc) 0-600
(@40Vdc) 0-1400
0-5Vdc: 2K min.

***Response Time: (90%) 250ms
Field Adjustable Cal: ± 10%
Temperature Range: -10°C to +60°C
Temperature Effect: ±1.0% of Rdg, ±0.1% F.S. output
Instrument Power: 85-135Vac, 50-400Hz, 5VA
“E” Option: 105-135Vac, 50-400Hz, 5VA
“-22” Option: 230Vac, 50/60Hz,±10%

APPLICATIONS
  • Equipment power consumption.
  • For use with SCR controls, chopped waveforms, or where harmonic components exist.
  • Standard outputs provide signal for interface with meters, recorders, or data acquisition equipment.
FEATURES
  • Accurate regardless of variations in voltage, current, power factor, or load.
  • Output is proportional to true power delivered to a load; P=EI(COS ø). Provides bi-directional operation.